Designing a plant; Reduction factors while laying cables in bunches and layers
There are following procedure to be adopted for correct dimensioning of a plant
(i) Load Analysis:-
First step in dimensioning of a plant is to check for connected load and their location
Now check for location of power distribution panels
Now we can calculate cable requirement i.e. length of cables and path of cable laying
Now we will do calculations of total power consumption while taking account utilization factors and demand factors
(ii) Transformer and generator size calculations:-
Transformer and generator size are usually selected 15-30% more in comparison to total connected load considering future prospectus.
(iii) Conductor size selection-
Now we calculate cable size according to load requirement of various connected loads. Cable selected may be copper or aluminum. Cables selection must also consider voltage drop at load current under specific reference conditions.
(iv) Selection of Protective circuit breaker:-
Short circuit calculations can be done and accordingly switchgear busbar and switchgear should be selected. It is always considered to select circuit breaker with breaking capacity higher than short circuit current. Rating of circuit breaker should be higher than rated current of load connected to circuit breaker. Characteristics of circuit breaker should be according to connected to load.
(v) Protection of conductors:-
For protection against overload circuit breaker rating should be higher than the load current but should be lower than Rated current carrying capacity of conductor.
In case of short circuit protection circuit breaker setting should be lower than short circuit current withstand by conductor.
(vi) Protection of Load:-
For protection of load such as motors which constitute 70% of total load of any industrial and commercial establishment overload relays and other protections must be provided after breaker so that tripping of relays leads to protection of load. For protection of human beings from electrical shocks it is always recommended to install RCCB or ELCB.
Selection of the cable
For installation and calculation of current carrying capacity of cables in Industrial, commercial and houses cable selection should be as per International standard IEC 60364-5-52 i.e. “Electrical installations of buildings Part 5-52 for “Selection and Erection of Electrical Equipment- Wiring systems”.
There are following ways and parameters are used to select the cable type:
a) Conductivity of Material:-
The foremost parameters to be considered while selection of cables is conductivity of material. Copper is costlier then aluminum but selection depends upon cost of material, size of material , weight of material, resistivity of material and resistivity to corrosive environment. Generally copper is having higher current carrying capacity i.e. 30% higher than aluminum conductors for same cross-sectional area, this is due to fact that aluminum is having higher resistivity than copper i.e. 60% higher than copper conductor.
b) Insulating Material used for conductors:-
There are so many insulating materials used for copper or aluminum conductors. Insulating material may or may not be used for conductors. Materials used for conductors may be PVC, XLPE. Insulating material will affects maximum temperature that a cable able to carry under normal and short circuit conditions.
c) Type of conductor:-
There are following types of conductors:-
a) Bare conductor
b) Single core cable without sheath
c) Single core cable with sheath
d) Multicore cable with sheath and armored
e) Flexible multicore cable
Cable can be selected according to mechanical resistance, degree of insulation and difficulty of installation required by the method of installation.
Conductors reduction factor while laying the cables in different arrangement of laying the cables:-
It has been observed that with presence of other cables laid around the cable , cable current carrying capacity is influenced significantly. This happens because heat dissipation of single cable get affected due to presence of other cables nearby.
Below we will discuss effect of other cables on current carrying capacity of single cable. For same there is factor K2 comes into picture according to installation of cables laid close together in layers or bunches.
The value of correction factor K2= 1 when:
Distance between two single core cables of different circuits is more than twice that of external diameter of the cable with larger cross section.
Adjacent cables are loaded less than 30% of current carrying capacity.
The correction factors for cables which are either bunched or laid in layers is usually calculated by assuming that all cables laid in bunches are similar cables and also load on cables is same. The calculation of the reduction factors for bunched cables with different crosssections depends on the number of cables and on their cross sections. These factors have not been tabled, but must be calculated for each bunch or layer.
The reduction factor for a group containing different cross sections of insulated conductors or cables in conduits, or cable ducting is:
where:
K2= 1/(n)1/2
• K2 is the group reduction factor;
• n is the number of circuits of the bunch.
The reduction factor obtained by this equation reduces the danger of overloading of cables with a smaller cross section, but may lead to under utilization of cables with a larger cross section. Such under utilization can be avoided if large and small cables are not mixed in the same group.
The following tables show the reduction factor (k2).
Reduction Factor for grouped cables:-
Item | Arrangement (Cables Touching) | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 12 | 16 | 20 | To be used with current- carrying capacities Reference |
1 | Bunched in air/ on a Surface/ enclosed | 1.00 | 0.80 | 0.70 | 0.65 | 0.60 | 0.57 | 0.54 | 0.52 | 0.50 | 0.45 | 0.41 | 0.38 | Method A to F |
2 | Single layer on wall, floor or flat tray | 1.00 | 0.85 | 0.79 | 0.75 | 0.73 | 0.72 | 0.72 | 0.71 | 0.70 | No further reduction factor for more than nine circuits or multicore cables | Method C | ||
3 | Single layer fixed directly under a wooden ceiling | 0.95 | 0.81 | 0.72 | 0.68 | 0.66 | 0.64 | 0.63 | 0.62 | 0.61 | ||||
4 | Single layer on perforated tray or vertical tray | 1.00 | 0.88 | 0.82 | 0.77 | 0.75 | 0.73 | 0.73 | 0.72 | 0.72 | Method E & F | |||
5 | Single layer on ladder support | 1.00 | 0.87 | 0.82 | 0.80 | 0.80 | 0.79 | 0.79 | 0.78 | 0.78 |
Comments
Post a Comment